EasyManua.ls Logo

Siemens SICAM - Primary Current Settings

Siemens SICAM
174 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
i
i
NOTE
If the CrossBlockTimer value is set as 0, then the fault indication is not blocked in case of an inrush-current
detection.
Primary Current Settings
Based on the selected current-transformer type, the rated primary current parameter can be set from 50 A to
1000 A via the user interface or Modbus registers.
After setting the parameters, connect the current inputs I
1
, I
2
/I
N
, I
3
via low-power current transformers (LoPo
CTs) or conventional current transformers (CT). For interfacing via conventional CTs, use a 1 A CT adaptor
(MLFB 6MD2320-0AA10-1AA0) or a 5 A CT adaptor (MLFB 6MD2320-0AA20-1AA0).
The LoPo CTs convert the primary current to a proportional output voltage. The device has a rated primary
current setting of 300 A (@ 225 mV).
Ground-Current Calculation
For solidly-grounded systems, the ground currents are calculated from the vector sum of 3 phases. The ground
current is also calculated for isolated/resonant-grounded systems, when the phase-current sensor for phase L2
is connected to the I
2
/I
N
terminal.
If the ground-current sensor is connected to the I
2
/I
N
terminal, the ground current can be measured for
isolated/resonant-grounded systems.
When the ground current is measured, the ground current can be configured from 25 A to 150 A.
For more information about the ground sensor, refer to Ground Sensor, Page 123.
The calculation/measurement of the ground current is determined by setting the Ground-current acquisition
parameter.
i
i
NOTE
When the cos φ/sin φ functionality is used in isolated or resonant-grounded systems, the deviation of the
ground current (I
dir
) calculated is within 3 A.
i
i
NOTE
For isolated systems, if the angle difference between V
NG
and I
N
is closer to 0°, the deviation of the calcu-
lated ground current (I
dir
) can be more than 3 A.
i
i
NOTE
For resonant-grounded systems, if the angle difference between V
NG
and I
N
is closer to 90°, the deviation of
the calculated ground current (I
dir
) can be more than 3 A.
i
i
NOTE
When the ground-current calculation is used with the vector method, the deviation of the calculated
ground current is 3 %.
For more information about ground-current calculation, refer to Ground-Current Acquisition, Page 122
4.1.26
4.1.27
Device Functions
4.1 Description
SICAM, Feeder Condition Monitor, Manual 51
E50417-H8940-C580-A4, Edition 03.2019

Table of Contents

Related product manuals