Angle Offset
(Address 87) This register defines the correction factor for the I
1
angle. It is expressed in minutes (min).
Bit 15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit signed integer
Unit min
Range -500 to 500
Default 0
I
2
/I
N
Magnitude Factor
(Address 88) This register defines the correction factor for the I
2
/I
N
magnitude.
Refer to I
1
Magnitude Factor, Page 129.
I
2
/I
N
Angle Offset
(Address 89) This register defines the correction factor for the I
2
/I
N
angle. It is expressed in minutes (min).
Refer to I
1
Angle Offset, Page 130.
I
3
Magnitude Factor
(Address 90) This register defines the correction factor for the I
3
magnitude.
Refer to I
1
Magnitude Factor, Page 129.
I
3
Angle Offset
(Address 91) This register defines the correction factor for the I
3
angle. It is expressed in minutes (min).
I
1
Angle Offset, Page 130.
Modbus Registers
B.4 Register-Type Data – Holding Registers
130 SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019