Format 16-bit unsigned integer
Unit 1/1000
Range 0, 700 to 3000
Default (correction factor disabled) 0
Default (correction factor enabled) 1000
V
1
Angle Offset
(Address 81) This register defines the correction factor for the V
1
angle. It is expressed in minutes (min).
Bit 15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit signed integer
Unit min
Range -500 to 500
Default 0
V
2
Magnitude Factor
(Address 82) This register defines the correction factor for the V
2
magnitude.
Refer to V
1
Magnitude Factor, Page 128.
V
2
Angle Offset
(Address 83) This register defines the correction factor for the V
2
angle. It is expressed in minutes (min).
Refer to V
1
Angle Offset, Page 129.
V
3
Magnitude Factor
(Address 84) This register defines the correction factor for the V
3
magnitude.
Refer to V
1
Magnitude Factor, Page 128.
V
3
Angle Offset
(Address 85) This register defines the correction factor for the V
3
angle. It is expressed in minutes (min).
Refer to V
1
Angle Offset, Page 129.
I
1
Magnitude Factor
(Address 86) This register defines the correction factor for the I
1
magnitude.
Bit
15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Unit 1/1000
Range 0, 800 to 1200
Default (correction factor disabled) 0
Default (correction factor enabled) 1000
Modbus Registers
B.4 Register-Type Data – Holding Registers
SICAM, Feeder Condition Monitor, Manual 129
E50417-H8940-C580-A4, Edition 03.2019