Format 16-bit unsigned integer
Unit
Range 1 to 100
Default 0
Nos. Det.
(Address 77) This register defines the counter threshold for intermittent ground-fault detection.
Bit 15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Range 2 to 900
Default 0
T-det. ext.
(Address 78) This register defines the time threshold for intermittent ground-fault detection. It is expressed in
seconds.
Bit 15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Unit s
Range 1 to 600
Default 0
Correction Factor
(Address 79) This register provides an option to enable or disable the correction factor for voltage and current
measurements.
Bit
15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Unit
Range 0 to 1
Default 0
V
1
Magnitude Factor
(Address 80) This register defines the correction factor for the V
1
magnitude.
Bit
15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Modbus Registers
B.4 Register-Type Data – Holding Registers
128 SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019