Modbus Register
Address
Parameter Individual Test Value Time Duration
9 Initiate auto calibration 1 5 s
10 Energy counter reset 1 5 s
11 Password reset 1 5 s
12 Active-group switching 1 5 s
Table B-18 Bit-Type Data Discrete Input
Modbus Register
Address
Parameter Individual Test Value Time Duration
1 Data available 1 5 s
2 Test mode act 1 Entire duration of self-
test mode
3 I>> 1 5 s
4 I
N
> 1 5 s
5 Overvoltage warning 1 5 s
6 Overvoltage alarm 1 5 s
7 Undervoltage warning 1 5 s
8 Undervoltage alarm 1 5 s
9 I>/I>> Dir A 1 5 s
10 I>/I>> Dir B 1 5 s
11 I
N
> Dir A 1 5 s
12 I
N
> Dir B 1 5 s
13 I
1
forward 1 5 s
14 I
1
reverse 1 5 s
15 I
2
forward 1 5 s
16 I
2
reverse 1 5 s
17 I
3
forward 1 5 s
18 I
3
reverse 1 5 s
19 Time sync required 1 5 s
20 I
max
warning 1 5 s
21 I
max
alarm 1 5 s
22 I> 1 5 s
23 Phase fault 1 5 s
24 Phase-fault indication (I>/I>>) for at
least 3 s
1 5 s
25 Device-health status 1 5 s
26 I
1
I>/I>> 1 5 s
27 I
2
I>/I>> 1 5 s
28 I
3
I>/I>> 1 5 s
29 Ground fault phase 1 1 5 s
30 Ground fault phase 2 1 5 s
31 Ground fault phase 3 1 5 s
32 Intermittent ground fault 1 5 s
33 Phase-sequence monitoring (ABC) 1 5 s
34 Phase-sequence monitoring (ACB) 1 5 s
Modbus Registers
B.9 Self-Test Mode
SICAM, Feeder Condition Monitor, Manual 157
E50417-H8940-C580-A4, Edition 03.2019