Programming
4.3 Time-based IO
High-precision input/output with Time-based IO
Function Manual, 08/2014, A5E33454822-AB
45
Table with error codes
Error code
Meaning
Remedy
(DW#16#...)
00000000
No error.
10010000 The assigned number of the digital input at the Channel
input parameter is outside the permitted range
(depending on addressed module and channel
configuration).
Correct the value at the Channel input
parameter.
10020000 The TIO_DI instruction is not called in an isochronous
OB. The instruction can only be used without errors in an
isochronous OB.
Make sure that TIO_DI is called in a
"Synchronous Cycle" OB.
10030000 An error occurred when reading the HWID input
parameter.
Check the value at the HWID input parameter.
Specify the hardware identifier of the TIO module
from its module properties in HWCN. An internal
system constant of data type Hw_SubModule is
available for the symbolic addressing.
x0040000 The data in TIO_SYNC_Data is invalid/incorrect. Check the TIO_SYNC instruction and the
interconnection of its TIO_SYNC_Data output.
1005xxxx
An error has occurred during execution of the RD_SINFO
system function. The low word xxxx displays the error
information of the RET_VAL return value from
RD_SINFO.
Read the description of the RD_SINFO in the
TIA Portal information system.
Make sure that TIO_DI is called in a
"Synchronous Cycle" OB.
10060000 Unable to find TM Timer DIDQ.
Possible cause:
The module configured using the hardware identifier is
not a TM Timer DIDQ.
Make sure that the configured module is a
TM Timer DIDQ.
Check the value at the HWID input
parameter. Specify the hardware identifier of
the TIO module from its module properties in
HWCN.
10070000 An internal error occurred during the address calculation. Check the value at the HWID input parameter.
Specify the hardware identif
ier of the TIO module
from its module properties in HWCN. An internal
system constant of data type Hw_SubModule is
available for the symbolic addressing.
00080000 TIO module is not synchronized using the TIO_SYNC
instruction.
Check the instruction TIO_SYNC.
10090000 The read cycle time of the isochronous OB is outside the
permitted range of 0 < T
APP
<= 16 ms and is therefore
invalid.
The instruction can only be used without errors in an
isochronous OB.
Correct the cycle time.
Make sure that TIO_DI is called in a
"Synchronous Cycle" OB.
100A0000 The assigned time at the TO input parameter is outside
the permitted range of 0 < T
o
<= 4 ms.
Correct the value at the TO input parameter.
100Bxxxx An error has occurred during execution of the RD_ADDR
system function. The low word xxxx displays the error
information of the RET_VAL return value from
RD_ADDR.
Read the description of the RD_ADDR in the
TIA Portal information system.