Programming
4.3 Time-based IO
High-precision input/output with Time-based IO
46 Function Manual, 08/2014, A5E33454822-AB
Error code
Meaning
Remedy
(DW#16#...)
000C0000 The converted time stamp is invalid.
Possible cause:
Communication error
Check the PROFINET communication with the
TIO module.
000D0000 The Quality Information of the digital input indicates that
an error has occurred at the digital input.
Check the wiring of the digital input.
000E0000 The assigned number at the Channel input parameter is
not a digital input configured as Timer DI.
Check the channel configuration (only for
TM Timer DIDQ 16x24V).
Check the operating mode of the digital input.
000F0000 The assigned value at the EdgeSel input parameter is
outside the valid range of 1 to 5.
Correct the value at the EdgeSel input
parameter.
10100000 The send clock is outside the permitted range of 0
< SendClock <= 4 ms and is therefore invalid.
The error code can also indicate that
The data in TIO_SYNC_Data is invalid or does not
exist.
The TIO_DI instruction is not called in an isochronous
OB.
Correct the send clock.
x0FF0000
General internal error.