EasyManua.ls Logo

Siemens SIMATIC ET 200AL - Page 159

Siemens SIMATIC ET 200AL
1585 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Wiring
3.3 Configuring PROFIBUS DP address and terminating resistor
Interface module IM 157-1 DP (6ES7157-1AA00-0AB0)
16 Manual, 12/2016, A5E32100641-AD
Pin assignment of the connector for infeed of the supply voltage
The following table shows the pin assignment of the connector for infeed of the supply
voltage.
Table 3- 3 Pin assignment of the supply voltage connector
Pin
Assignment
Assignment of the wire
color of the power line
cable
Front view of the
connector
X80 connector (power input)
1
Supply voltage 1L+ (non-switched)
Brown
2 Ground 2M (switched) White
3
Ground 1M (non-switched)
Blue
4 Load voltage 2L+ (switched) Black
Pin assignment of the socket for loop-through of the supply voltage
The table below shows the pin assignment of the socket for loop-through of the supply
voltage.
Table 3- 4 Pin assignment of the supply voltage socket
Pin
Assignment
Assignment of the wire
color of the power line
cable
Front view of the
socket
X81 Socket (power output)
1
Supply voltage 1L+ (non-switched)
Brown
2
Ground 2M (switched)
White
3
Ground 1M (non-switched)
Blue
4 Load voltage 2L+ (switched) Black
NOTICE
ET-Connection/supply voltage
Observe the correct wiring of the M8 sockets for ET-Connection and the supply voltage.
Mixing up the ET-Connection connectors and the connectors for the supply voltage can
destroy the module.

Table of Contents

Other manuals for Siemens SIMATIC ET 200AL

Related product manuals