Technical specifications
Communication module CM 4xIO-Link 4xM12(6ES7147-5JD00-0BA0)
30 Manual, 10/2017, A5E32352322-AE
• Short-circuit protection
Yes; per module, electronic
• Output current, max.
1.4 A; Total current of all ports
• of which simultaneously controllable
4
Transmission rate 4.8 kBaud (COM1); 38.4 kBaud (COM2),
Size of process data, input per port
Size of process data, input per module
Size of process data, output per port
Size of process data, output per module
Memory size for device parameter
Possible with function block IO_LINK_MASTER
Configuration without S7-PCT
Possible; autostart/manual function
Cable length unshielded, max.
• IO-Link
Yes
• DI
Yes
• DQ
Yes; max. 100 mA
Connection of IO-Link devices
• Port type A
Yes; via 3-core cable
• Port type B
Yes; Additional device supply: 1.6 A total current
Interrupts/diagnostics/status information
• Diagnostic alarm
Yes; Parameterizable
• Monitoring the supply voltage
Yes
• Wire-break
Yes
• Short-circuit
Yes