Alarms
6.5 Example program for program alarms
Diagnostics
Function Manual, 09/2016, A5E03735838-AD
93
6. Add another entry in the text list.
7. Enter the alarm text for the minimum fill level in the "Entry" column.
Figure 6-15 Creating a text list
Result: You have created the text list for the alarm text.
Edit alarm text
To edit the alarm text for the example program, follow these steps:
1. Double-click "PLC supervisions & alarms" in the project tree. Select the "Alarms" tab. The
alarm editor opens.
2. Select the type alarm created for the example.
3. Click in the "Alarm text" column.
4. Open the shortcut menu and select the command "Insert a dynamic parameter (text list)".
Figure 6-16 Edit alarm text