Maintenance
9.1 Replacing modules
Distributed I/O system
System Manual, 02/2018, A5E31861578-AF
79
4. Replace the module.
Note
"New" module
The removed module may only be repla
ced by a module of the same type.
5. Fasten the module with a torque of 1.2 Nm.
6. Connect all cables.
7. Turn the supply voltage on.
WARNING
Pay attention to the slot number of the module
If you mix up the ET 200AL I/O modules when connecting them, this can cause personal
injury and damage to the machine.
The ET 200AL distributed I/O system cannot distinguish between modules of the same type
during the actual/target comparison.
We recommend that you clearly label the ET 200AL I/O modules with the slot number.
The figure below shows a recommendation for labeling the ET 200AL I/O modules with the
slot number.
Recommendation for labeling the slot number
Figure 9-1 Slot number
Result
The disconnected I/O module and all downstream I/O modules start up again by themselves.