Programming
5.4 Addressing function blocks
ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
36 Manual, 06/2019, A5E46959434-AA
Parameter
The following table shows the parameters of the function block:
Parameter
Declaration
Data type
Memory
area
Description
CHANGE Input
BOOL I, Q, M, D,
L or Con-
stant
Change the short address of the specific device upon a rising edge.
DEV_TYP
E
USInt I, Q, M, D,
L or Con-
stant
Select the device type:
1: Control gear
2: Input device (Sensor)
OLD_ADD
R
BOOL I, Q, M, D,
L or Con-
stant
The current short address of the device.
NEW_AD
DR
USInt I, Q, M, D,
L or Con-
stant
The short address to be assigned to the device.
CM_DALI InOut "DALI_CT
RL"
The data block of
DALI_CTRL
specifies the CM 1xDALI which com-
municates with the current function block.
BUSY Output BOOL I, Q, M, D,
L
Status parameter:
BUSY = 0: Processing of job is terminated.
BUSY = 1: Job is still being committed.
ACTIVE BOOL I, Q, M, D,
L
Status parameter:
ACTIVE = 0: Job is not yet started.
ACTIVE = 1: Job is being executed.
DONE BOOL I, Q, M, D,
L
Status parameter:
DONE = 0: Job is not yet started or still executing.
DONE = 1: Job is executed without errors.
ERROR BOOL I, Q, M, D,
L
Status parameter:
ERROR = 0: No error occurs.
ERROR = 1: Error occurs during processing.
STATUS BYTE I, Q, M, D,
L
When ERROR = 0, STATUS has
following three values:
16#00: Idle
16#01: Executing
16#7F: Completed
When ERROR = 1, STATUS
shows the detailed error code. For
the detailed meaning of each
error code, refer to Parameter
STATUS (Page 106).