The following table shows the parameters of the function block:
SET Input
BOOL I, Q, M, D,
L or Con-
Set the operation hour upon a rising edge.
ADDRES
S
USInt I, Q, M, D,
L or Con-
Specify the short address of the device.
Range: 0 to 63
OPHOUR UInt I, Q, M, D,
L or Con-
Set the operation hour to the control gear.
CM_DALI InOut "DALI_CT
The data block of
specifies the CM 1xDALI which com-
municates with the current function block.
BUSY Output BOOL I, Q, M, D,
L
Status parameter:
• BUSY = 0: Processing of job is terminated.
• BUSY = 1: Job is still being committed.
ACTIVE BOOL I, Q, M, D,
L
Status parameter:
• ACTIVE = 0: Job is not yet started.
• ACTIVE = 1: Job is being executed.
DONE BOOL I, Q, M, D,
L
Status parameter:
• DONE = 0: Job is not yet started or still executing.
• DONE = 1: Job is executed without errors.
ERROR BOOL I, Q, M, D,
L
Status parameter:
• ERROR = 0: No error occurs.
• ERROR = 1: Error occurs during processing.
STATUS BYTE I, Q, M, D,
L
When ERROR = 0, STATUS has
following three values:
• 16#00: Idle
• 16#01: Executing
• 16#7F: Completed
When ERROR = 1, STATUS
shows the detailed error code. For
the detailed meaning of each
error code, refer to Parameter
STATUS (Page 106).
DALI_SENSOR_STATUS
Description
DALI_SENSOR_STATUS
is used for querying the status of one sensor (input device). The
status information is queried from the physical DALI device (refer to data flow path 6
(Page 23)). The status information saved in CM 1xDALI will be updated (refer to data flow
path 4 (Page 23)).