Programming
5.7 Configuration function blocks
ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
Manual, 06/2019, A5E46959434-AA
97
Table 5- 4 Sensor instance type-related parameters
Attributes
BYTE
Type 1 (push button)
Type 2 (absolute input)
Type 3 (occupancy)
Type 4 (light sensor)
Read/Write
0
tShort
Deadtime
Hold time
Hysteresis
1
tDouble
Report time Report time Hysteresis min
2
tRepeat
Not used
Deadtime
Report time
3
tStuck
Not used Deadtime
Read only
4
Resolution
5
tShortMin Not used Not used Not used
6
5.7.16
DALI_SENSOR_SET_INST_PARAM
Description
DALI_SENSOR_INST_PARAM
is used for setting the instance parameters of the input
device (sensor).
If the status of the sensor is configured (for example, sensor is added by using
DALI_SENSOR_ADD (Page 89)), the parameters are saved in the CM 1xDALI (refer to
data flow path 1 (Page 23)) and sent to the physical device (refer to data flow path 5
(Page 23)).
If the status of the sensor is not configured, the parameters are only sent to the physical
device (refer to data flow path 5 (Page 23)).
You can query the instance parameters of the sensor by using
DALI_SENSOR_QUERY_INST_PARAM (Page 95).