Programming
5.7 Configuration function blocks
ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
Manual, 06/2019, A5E46959434-AA
91
DALI_SENSOR_DELETE
Description
DALI_SENSOR_DELETE
is used for deleting one configured sensor, including its instances.
This function block does not send any command to the DALI bus, but deletes the device
which is added by using DALI_SENSOR_ADD (Page 89) and the data which is saved in the
CM 1xDALI (refer to data flow path 1 (Page 23)).
The following table shows the parameters of the function block:
DELETE Input
BOOL I, Q, M, D,
L or Con-
Delete one configured sensor upon a rising edge.
ADDRES
S
USInt I, Q, M, D,
L or Con-
Specify the short address of the device.
Range: 0 to 63
CM_DALI InOut "DALI_CT
The data block of
specifies the CM 1xDALI which com-
municates with the current function block.
BUSY Output BOOL I, Q, M, D,
L
Status parameter:
• BUSY = 0: Processing of job is terminated.
• BUSY = 1: Job is still being committed.
ACTIVE BOOL I, Q, M, D,
L
Status parameter:
• ACTIVE = 0: Job is not yet started.
• ACTIVE = 1: Job is being executed.
DONE BOOL I, Q, M, D,
L
Status parameter:
• DONE = 0: Job is not yet started or still executing.
• DONE = 1: Job is executed without errors.
ERROR BOOL I, Q, M, D,
L
Status parameter:
• ERROR = 0: No error occurs.
• ERROR = 1: Error occurs during processing.
STATUS BYTE I, Q, M, D,
L
When ERROR = 0, STATUS has
following three values:
• 16#00: Idle
• 16#01: Executing
• 16#7F: Completed
When ERROR = 1, STATUS
shows the detailed error code. For
the detailed meaning of each
error code, refer to Parameter
STATUS (Page 106).