Programming
5.7 Configuration function blocks
ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
Manual, 06/2019, A5E46959434-AA
95
5.7.15
DALI_SENSOR_QUERY_INST_PARAM
Description
DALI_SENSOR_QUERY_INST_PARAM
is used for querying the instance parameters of the
input device (sensor).
When you set the input "PHY_DEV" to 1, this function block queries the parameters from
the physical device (refer to data flow path 6 (Page 23)).
When you set the input "PHY_DEV" to 0, this function block queries the parameters which
are saved in CM 1xDALI (refer to data flow path 2 (Page 23)).
You can set the instance parameters of sensor by using
DALI_SENSOR_SET_INST_PARAM (Page 97).
Parameter
The following table shows the parameters of the function block:
Parameter
Declaration
Data type
Memory
area
Description
QUERY Input
BOOL I, Q, M, D,
L or Con-
stant
Query the instance parameters of the sensor upon a rising edge.
ADDRESS USInt I, Q, M, D,
L or Con-
stant
Specify the short address of the device.
Range: 0 to 63
INST_NUM USInt I, Q, M, D,
L or Con-
stant
Specify the instance number.
Range: 0 to 31
PHY_DEV BOOL I, Q, M, D,
L or Con-
stant
Specify the location of parameters:
PHY_DEV = 0 : Query the parameters which are saved in CM
1xDALI.
PHY_DEV = 1 : Query the parameters from the physical device
by sending commands.
CM_DALI InOut "DALI_CT
RL"
The data block of
DALI_CTRL
specifies the CM 1xDALI which
communicates with the current function block.
BUSY Output BOOL I, Q, M, D,
L
Status parameter:
BUSY = 0: Processing of job is terminated.
BUSY = 1: Job is still being committed.