5.5 Control gear dimming function blocks
ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
50 Manual, 06/2019, A5E46959434-AA
Parameter
Declaration
Data type
Memory
area
Description
TEMPER
ATURE
UInt The color value of temperature.
T
C
(K) = 1000000 / "TEMPERATURE"
Range: 1 to 65534
CM_DALI InOut "DALI_CT
RL"
The data block of
DALI_CTRL
specifies the CM 1xDALI which
communicates with the current function block.
BUSY Output BOOL I, Q, M, D,
L
Status parameter:
BUSY = 0: Processing of job is terminated.
BUSY = 1: Job is still being committed.
ACTIVE BOOL I, Q, M, D,
L
Status parameter:
ACTIVE = 0: Job is not yet started.
ACTIVE = 1: Job is being executed.
DONE BOOL I, Q, M, D,
L
Status parameter:
DONE = 0: Job is not yet started or still executing.
DONE = 1: Job is executed without errors.
ERROR BOOL I, Q, M, D,
L
Status parameter:
ERROR = 0: No error occurs.
ERROR = 1: An error occurs during processing.
STATUS BYTE I, Q, M, D,
L
When ERROR = 0, STATUS has
following three values:
16#00: Idle
16#01: Executing
16#7F: Completed
When ERROR = 1, STATUS
shows the detailed error code.
For the detailed meaning of each
error code, refer to Parameter
STATUS (Page 106).
5.5.7
DALI_ECG_GOTO_SCENE
Description
DALI_ECG_GOTO_SCENE
is used for setting control gears to go to the specified scene
(refer to data flow path 5 (Page 23)). You can also query or configure the scene information
by using DALI_ECG_QUERY_SCENE (Page 85) or DALI_ECG_SET_SCENE (Page 87).