Programming
5.5 Control gear dimming function blocks
ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
Manual, 06/2019, A5E46959434-AA
51
The following table shows the parameters of the function block:
GOTO Input
BOOL I, Q, M, D,
L or Con-
Go to the specified scene upon a rising edge.
GROUP BOOL I, Q, M, D,
L or Con-
stant
Specify the short address or group address of the control gear:
• GROUP = 0: ADDRESS indicates the short address or broadcast.
• GROUP = 1: ADDRESS indicates the group address.
ADDRES
S
USint I, Q, M, D,
L or Con-
stant
Identify the address information of the CM 1xDALI.
When GROUP = 0, ADDRESS
indicates the short address or
broadcast:
• 0 to 63: Specify the short
address of the device
• 253: Broadcast the un-
addressed devices
• 255: Broadcast all the devices
When GROUP = 1, ADDRESS
indicates the group address:
• 0 to 15: Group address
SCENE_N
UM
USint I, Q, M, D,
L or Con-
Go to the specified scene.
Range: Less than 16
CM_DALI InOut "DALI_CT
The data block of
specifies the CM 1xDALI which com-
municates with the current function block.
BUSY Output BOOL I, Q, M, D,
L
Status parameter:
• BUSY = 0: Processing of job is terminated.
• BUSY = 1: Job is still being committed.
ACTIVE BOOL I, Q, M, D,
L
Status parameter:
• ACTIVE = 0: Job is not yet started.
• ACTIVE = 1: Job is being executed.
DONE BOOL I, Q, M, D,
L
Status parameter:
• DONE = 0: Job is not yet started or still executing.
• DONE = 1: Job is executed without errors.
ERROR BOOL I, Q, M, D,
L
Status parameter:
• ERROR = 0: No error occurs.
• ERROR = 1: Error occurs during processing.
STATUS BYTE I, Q, M, D,
L
When ERROR = 0, STATUS has
following three values:
• 16#00: Idle
• 16#01: Executing
• 16#7F: Completed
When ERROR = 1, STATUS
shows the detailed error code. For
the detailed meaning of each
error code, refer to Parameter
STATUS (Page 106).