Programming
5.6 Diagnostic function blocks
ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
Manual, 06/2019, A5E46959434-AA
63
Parameter DEV_STATUS
Each Bit of the DEV_STATUS indicates the different status:
Bit
Status
Explanation
Bit 0
Input device error
The input device or its instances has an error.
Bit 1 Quiescent mode The input device does not produce any forward frame.
Bit 2 Short address is
mask (255)
No short address is assigned to this device.
Bit 3 Application active The application controller is active
Bit 4 Application con-
troller error
This application controller has an error.
Bit 5
Power cycle seen
An external power cycle is occurred.
Bit 6
Reset state
All the parameters of this device are at their reset value.
Bit 7
Unused
Unused
5.6.7
DALI_SENSOR_INPUT
Description
DALI_SENSOR_INPUT
is used for querying the input value of one instance in the input
device (sensor). The input value is queried from the physical DALI device (refer to data flow
path 6 (Page 23)).