Programming
5.7 Configuration function blocks
ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
98 Manual, 06/2019, A5E46959434-AA
Parameter
The following table shows the parameters of the function block:
Parameter
Declaration
Data type
Memory
area
Description
SET Input
BOOL I, Q, M, D,
L or Con-
stant
Set the instance parameters of the sensor upon a rising edge.
ADDRESS USInt I, Q, M, D,
L or Con-
stant
Specify the short address of the device.
Range: 0 to 63
INST_NUM USInt I, Q, M, D,
L or Con-
stant
Specify the instance number.
Range: 0 to 31
INST_PRM_
SET
InstPrm-
SetDetail
D, L The instance parameters of the input device (sensor).
INST_TY
PE
USInt Refer to the Instance type of input device (Page 107) to set the
instance type.
Range: 1 to 4
INST_AC
TIVE
BOOL Activation of the instance.
EVENT_
SCHEM
E
USInt An instance of an input device uses the selected event source ad-
dressing according to the scheme:
0: Instance type and instance number
1: Short address and instance type
2: Short address and instance number
3: Device group and instance number
4: Instance group and instance type
EVENT_
FILTER
BYTE The event message filter can be used to enable and disable specific
events. Refer to Description for EVENT_FILTER (Page 107) for the
detailed description.
INST_TYPE = 1 (push button), EVENT_FILTER is in the range
of 0 to 16#FF.
INST_TYPE = 2 (absolute input device), EVENT_FILTER is in
the range of 0 to 16#01.
INST_TYPE = 3 (occupancy sensor), EVENT_FILTER is in the
range of 0 to 16#1F.
INST_TYPE = 4 (light sensor), EVENT_FILTER is in the range
of 0 to 16#01.
EVENT_
PRIO
USInt The sending priority of the event message. The system reactions
are sent according to the set priority. The system reactions with
high priority take precedence over the system reactions with low
priority.
TYPE_P
RM_SET
1
Array[0..6]
of BYTE
The type-related parameters of the instance.