Programming
5.6 Diagnostic function blocks
ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
Manual, 06/2019, A5E46959434-AA
61
The following table shows the parameters of the function block:
READ Input
BOOL I, Q, M, D,
L or Con-
Query the status of sensor upon a rising edge.
ADDRESS USInt I, Q, M, D,
L or Con-
Specify the short address of the device.
Range: 0 to 63
CM_DALI InOut "DALI_CT
The data block of
specifies the CM 1xDALI which
communicates with the current function block.
BUSY Output BOOL I, Q, M, D,
L
Status parameter:
• BUSY = 0: Processing of job is terminated.
• BUSY = 1: Job is still being committed.
ACTIVE BOOL I, Q, M, D,
L
Status parameter:
• ACTIVE = 0: Job is not yet started.
• ACTIVE = 1: Job is being executed.
DONE BOOL I, Q, M, D,
L
Status parameter:
• DONE = 0: Job is not yet started or still executing.
• DONE = 1: Job is executed without errors.
ERROR BOOL I, Q, M, D,
L
Status parameter:
• ERROR = 0: No error occurs.
• ERROR = 1: Error occurs during processing.
STATUS BYTE I, Q, M, D,
L
When ERROR = 0,
STATUS has following
three values:
• 16#00: Idle
• 16#01: Executing
• 16#7F: Completed
When ERROR = 1, STATUS shows the
detailed error code. For the detailed
meaning of each error code, refer to Pa-
rameter STATUS (Page 106).
SENSOR_S
TATUS
SensorSta
Sta-
D, L The status information of sensor
CONFIG
URED
BOOL CONFIGURED = 1: The short address is configured by using
DALI_SENSOR_ADD (Page 89) or
DALI_DEV_UPLOAD
ADDR_C
HANGE
D
BOOL
• ADDR_CHANGED = 0: The short address of sensor is not
changed.
• ADDR_CHANGED = 1: The short address of sensor is changed
during the scan procedure.