Programming
5.7 Configuration function blocks
ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
88 Manual, 06/2019, A5E46959434-AA
Parameter
Declaration
Data
type
Memory
area
Description
COOR
DINAT
E_X
UInt The x-coordinate value of the point in the CIE color
space chromaticity diagram.
X-coordinate = "COORDINATE_X" * 1/65536.
Range: 0 to 65534
COOR
DINAT
E_Y
UInt The y-coordinate value of the point in the CIE color
space chromaticity diagram.
Y-coordinate = "COORDINATE_Y" * 1/65536.
Range: 0 to 65534
TEMPE
RATUR
E
UInt The color value of temperature.
T
C
(K) = 1000000 / "TEMPERATURE"
Range: 1 to 65534
CM_DALI InOut "DALI_
CTRL"
The data block of
DALI_CTRL
specifies the CM 1xDALI
which communicates with the current function block.
BUSY Output BOOL I, Q, M, D,
L
Status parameter:
BUSY = 0: Processing of job is terminated.
BUSY = 1: Job is still being committed.
ACTIVE BOOL I, Q, M, D,
L
Status parameter:
ACTIVE = 0: Job is not yet started.
ACTIVE = 1: Job is being executed.
DONE BOOL I, Q, M, D,
L
Status parameter:
DONE = 0: Job is not yet started or still executing.
DONE = 1: Job is executed without errors.
ERROR BOOL I, Q, M, D,
L
Status parameter:
ERROR = 0: No error occurs.
ERROR = 1: Error occurs during processing.
STATUS BYTE I, Q, M, D,
L
When ERROR = 0,
STATUS has following
three values:
16#00: Idle
16#01: Executing
16#7F: Completed
When ERROR = 1,
STATUS shows the de-
tailed error code. For the
detailed meaning of each
error code, refer to Pa-
rameter STATUS
(Page 106).