Technical specifications
7.1 Technical specifications
Analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF (6ES7136-6AA00-0CA1)
66 Manual, 08/2018, A5E41448857-AB
Connection of signal encoders
• for current measurement as 2-wire transducer
Yes
– Burden of 2-wire transmitter, max.
650 Ω
• for current measurement as 4-wire transducer
Yes
Linearity error (relative to input range), (+/-)
Temperature error (relative to input range), (+/-)
Repeat accuracy in steady state at 25 °C (relative to
0.1 %
Operational error limit in overall temperature range
• Current, relative to input range, (+/-)
2 %
Basic error limit (operational limit at 25 °C)
• Current, relative to input range, (+/-)
0.1 %
Interference voltage suppression for f = n x (f1 +/- 1 %),
f1 = interference frequency
• Series mode interference (peak value of interfer-
ence < rated value of input range), min.
40 dB
• Common mode interference, min.
70 dB
Interrupts/diagnostics/status information
Diagnostics function Yes, "Alarms/diagnostic messages" section
• Diagnostic alarm
Yes
• Limit value alarm
Yes
• Monitoring the supply voltage
Yes
• Wire-break
Yes; Measuring range 4 to 20 mA only
• Short-circuit
Yes
Diagnostics indication LED
• RUN LED
Yes; Green LED
• ERROR LED
Yes; Red LED
• Monitoring of the supply voltage (PWR-LED)
Yes; green PWR LED
• Channel status display
Yes; Green LED
• for channel diagnostics
Yes; Red LED
• for module diagnostics
Yes; Green/red LED