Interrupts/diagnostic messages
6.4 Diagnostic messages
ET 200SP F-TM Count 1x1Vpp sin/cos HF (6ES7136-6CB00-0CA0)
78 Equipment Manual, V1.0, 01/2021, A5E47073911-AA
Diagnostics alarm Fault
code
Meaning Solution
No pulses detected
16#030A
The expected number of pulses was not
received within a given revolution, where
the revolution is determined by the mod-
ule receiving an active N signal event.
Possible causes:
There is a faulty N signal.
The "Pulses per revolution" configura-
tion does not match the encoder's
pulses per revolution.
The module is configured to use the N
signal, but the encoder does not use
an N signal or there is a wire break.
There is noise on the N signal line.
Check the N signal process wiring.
Check the parameter is set to
match the sinusoidal cycles per
revolution.
F-address memory not
accessible
16#030D
The F-source address and F-destination
address stored in the coding element
cannot be accessed.
Verify that the coding element is pre-
sent or replace the coding element.
No valid F-address availa-
ble
16#030E
The electronic coding element contains
an invalid F-address.
Assign a PROFIsafe address to the F-
module.
Module is defective
16#0100
Possible causes:
Impermissibly high electromagnetic
interference is present.
The F-module has detected an internal
error and has reacted in a safety-
related manner.
Encoder frequencies received above
250kHz. In this situation, the module
is not defective.
Eliminate the interference. The
module must then be pulled and
plugged, or the power switched
OFF and ON.
Ensure encoder frequencies below
200kHz and reapply power to the
module.
Replace defective F-module.
Watchdog tripped
16#0103
Possible causes:
Impermissibly high electromagnetic
interference is present.
The F-module has detected an internal
error and has reacted in a safety-
related manner.
Undertemperature
16#0312
The minimum permissible temperature
limit has been violated.
Operate the F-module within the
specified temperature range (see
Technical Specifications).
Once the temperature has in-
creased and returns to the specified
range, the F-module must be re-
moved and reinserted or the power
switched OFF and ON.