Parameters/address space
4.6 Explanation of parameters
ET 200SP F-TM Count 1x1Vpp sin/cos HF (6ES7136-6CB00-0CA0)
36 Equipment Manual, V1.0, 01/2021, A5E47073911-AA
4.6 Explanation of parameters
4.6.1 F-parameters
Manual assignment of F-monitoring time
This is a selection to enable the "Manual assignment of F-monitoring time".
F-monitoring time
The monitoring time of safety-related PROFIsafe communication occurring between the F-
CPU and the F-I/O module.
F-source address
A unique network-wide address for the fail-safe CPU assigned to the F-CPU with the "Central
F-source address" parameter.
F-destination address
A unique F-destination address for each fail-safe module.
F-parameter signature (with addresses)
A signature for all F-parameters including F-addresses; used to easily determine whether
parameterization changes have occurred.
F-parameter signature (without addresses)
Signature for all F-parameters without F-addresses; used to easily determine whether
parameterization changes have occurred.
Behavior after channel fault
Specifies a passivation response by the F-TM Count module to channel faults. (Always set to
"Passivate channel" for the F-TM Count module since there is a single channel.)
Reintegration after channel fault
Specifies a switchover from fail-safe values to process data (reintegration) after channel
faults are eliminated. (Always set to "All channels manually" for the F-TM Count module since
RIOforFA is not supported.)