Parameters/address space
4.2 Reinitialize on parameterization download
ET 200SP F-TM Count 1x1Vpp sin/cos HF (6ES7136-6CB00-0CA0)
32 Equipment Manual, V1.0, 01/2021, A5E47073911-AA
4.2 Reinitialize on parameterization download
Each time parameterization of the F-module occurs, reinitialization of internal module states
is required. This means that internal module states are equivalent to power-up states.
Reinitializing results in the following changes in the module:
Process image status and event bits are reset
Counter value is reinitialized to the start value
Measured value calculations are reinitialized
Process image command enables are reset
Safety monitoring intermediate values are reset (for example, intermediate values
associated with SOS, SDI, and SLS calculations)
In addition to a user commanded download of parameters from STEP 7 (TIA Portal),
parameters will be downloaded, and the counter module will be reinitialized in the following
circumstances:
Power cycling of the F-CPU
Pull/Plug of the module
Power cycling the 24V user power to the module
Power cycling of the IM on a remote rack
Pull/Plug of the PROFInet cable to the IM remote rack