Protection
6.4 Know-how protection
CPU 1516pro-2 PN (6ES7516-2PN00-0AB0)
Operating Instructions, 09/2016, A5E35873416-AA
63
6.4
Know-how protection
Application
You can use know-how protection to protect one or more blocks of the OB, FB, FC type and
global data blocks in your program from unauthorized access. You can enter a password to
restrict access to a block. The password offers high-level protection against unauthorized
reading or manipulation of the block.
Readable data
If a block is know-how protected, only the following data is readable without the correct
password:
Block title, comments and block properties
Block parameters (INPUT, OUTPUT, IN, OUT, RETURN)
Call structure of the program
Global tags without information on the point of use
Further actions
Further actions that can be carried out with a know-how protected block:
Copying and deleting
Calling within a program
Online/offline comparison
Load
Global data blocks and array data blocks
You cannot provide global data blocks (global DBs) with know-how protection. Users who do
not possess the valid password can read the global data block but not change it.
You cannot provide array data blocks (array DBs) with know-how protection.