Data Blocks/Error Lists
C-13
FM 351 Positioning Module
C79000-G7076-C351-02
C.4 List of JOB_ERR Messages
JOB_ERR
(hex)
JOB_ER
R (dec)
JOB_ER
R (int)
Meaning
80A0 32928 32608 Negative acknowledgment when reading from module.
Module removed during read operation or module
defective.
80A1 32929 32607 Negative acknowledgment when writing to module. Module
removed during write operation or module defective.
80A2 32930 32606 DP protocol error at layer 2
80A3 32931 32605 DP protocol error at user interface / user
80A4 32932 32604 Communication problem on K bus
80B0 32944 32592 Data record/job unknown.
80B1 32945 32591 Specified length wrong. Incorrectly set FM_TYPE
parameter in the channel DB for the module in use.
80B2 32946 32590 The configured slot is empty.
80B3 32947 32589 Actual module type does not match configured module
type.
80C0 32960 32576 The module does not have the data to be read.
80C1 32961 32575 The data of a write job of the same type have not yet been
processed on the module.
80C2 32962 32574 The module is currently processing the maximum number
of jobs.
80C3 32963 32573 Required resources (memory etc.) currently in use.
80C4 32964 32572 Communication error
80C5 32965 32571 Distributed I/Os not available.
80C6 32966 32570 Priority class abort (warm restart or background)
8522 34082 31454 Channel DB or parameter DB too short. The data cannot be
read from the DB. (write job)
8532 34098 31438 DB number of the parameter DB too high. (write job)
853A 34106 31430 Parameter DB does not exist. (write job)
8544 34116 31420 Error in nth (n > 1) read access to a DB after error occurred.
(write job)
8723 34595 30941 Channel DB or parameter DB too short. The data cannot be
written to the DB. (read job)
8730 34608 30928 Parameter DB on the CPU write-protected. The data
cannot be written to the DB (read job).
8732 34610 30926 DB number of the parameter DB too high. (read job)
873A 34618 30918 Parameter DB does not exist. (read job)

Table of Contents

Other manuals for Siemens SIMATIC FM 351