Data Blocks/Error Lists
C-22
FM 351 Positioning Module
C79000-G7076-C351-02
Class 6: Incremental Dimension Table Errors
The incremental dimension table errors do not lead to an error reaction.
No. Meaning Diagnostic
Interrupt
6
Incremental dimension specified in the incremental
dimension table too high
No
Cause
The value is outside $100 m or $1000 m. The
distance/ target must be greater than the travel
range
On a rotary axis, the coordinate must be > = 0 and
less than the end of the rotary axis.
Class 15: Messages
Messages do not lead to an error reaction.
No. Meaning Diagnostic
Interrupt
1
Start of parameter assignment No
Cause
The module has detected a parameter assignment
by a system data block.
2
End of parameter assignment No
Cause
The module has processed the parameter
assignment by a system data block error-free.
11
Not enough distance to switchover point No
Cause
The hardware response times cannot be maintained
since the interval between the switching points is too
small.
12
Not enough distance to reversal point No
Cause
The hardware response times cannot be maintained
since the interval between the switching points is too
small.
14
Not enough distance to switch-off point No
Cause
The hardware response times cannot be maintained
since the interval between the switching points is too
small.
15
Not enough distance to start of target range No
Cause
The hardware response times cannot be maintained
since the interval between the switching points is too
small.