Data Blocks/Error Lists
C-25
FM 351 Positioning Module
C79000-G7076-C351-02
No. Diagnostic
Interrupt
Meaning
146
Incremental encoder missing pulses Yes
Cause
Encoder monitoring has detected missing pulses.
Number of increments per encoder revolution is
incorrectly entered.
Encoder defective: Does not supply the specified
number of pulses.
Incorrect or missing zero marker.
Interference affecting the encoder cable.
Effect
Positioning is aborted.
Switching off the outputs
Start enable is deleted.
Remedy
Enter the number of increments/encoder
revolution correctly (parameter dialog).
Check the encoder and encoder cable.
Keep to shielding and grounding regulations.
Monitoring can be temporarily suppressed at the
operators risk by setting parameters in the
parameter dialog.