Setting parameters for blocks
3.4 Programming Ident blocks
Ident profile and Ident blocks, standard function for Ident systems
Function Manual, 10/2018, C79000-G8976-C387-04
55
3.4.3.5
Reset_RF300
Figure 3-27 "Reset_RF300" block
Table 3- 32 Explanation of the "Reset_RF300" block
Parameter
Data type
Default values
Description
TAG_CONTROL Byte 1 Presence check
0 = Off
1 = on
4 = presence (antenna is off. The
antenna is turned on only when a
Read or Write command is sent.)
TAG_TYPE Byte 0 Transponder type:
1 = every ISO transponder
0 = RF300 transponder
RF_POWER Byte 0 Output power; only relevant for
RF380R
RF power from 0.5 W to 2 W in incre-
ments of 0.25 W (range of values:
0x02 ... 0x08).
Default value: 0x00 1.25 W.
This setting is not necessary with the
RF380R readers of the 2nd generation
(6GT2801-3BAx0) because the power
limits are optimized automatically
depending on the reader-transponder
distance.