Setting parameters for blocks
3.5 Programming the Ident profile
Ident profile and Ident blocks, standard function for Ident systems
Function Manual, 10/2018, C79000-G8976-C387-04
81
3.5.4.2
Commands
All relevant parameters and parameter values for the individual commands are listed below.
Parameters that are not listed receive the default value specified in the previous section.
Table 3- 56 PHYSICAL-READ
Parameter
Value / description
CMD
0x70
OFFSETBUFFER
Offset in the "RXREF" receive buffer
LEN_DATA Length of received data
RF300 Gen1: Max. 57,085 bytes per read operation
ADDR_TAG
Address on the transponder
CHAINED
True = chained
False = not chained
EPCID_UID Buffer for up to 62 bytes EPC-ID, 8 bytes UID or 4 bytes handle ID.
2 - 62-byte EPC-ID is entered at the start of the buffer (length is
set by "LEN_ID")
8-byte UID is entered at the start of the buffer ("LEN_ID = 8")
4-byte handle ID must be entered in the array element [5]-[8]
("LEN_ID = 8")
Default value: 0x00 unspecified single tag access
LEN_ID Length of the EPC-ID (2-62 bytes)
0x00 ≙ unspecified single tag access
MEM_BANK Memory bank
0x00 ≙ Reserved
0x01 ≙ EPC
0x02 ≙ TID
0x03 ≙ USER
PSWD Password
0x00 ≙ no password
RXREF
Read data