Description
3.3 Features
SIMATIC IPC427C
14 Operating Instructions, 04/2009, A5E02414743-01
Basic data
Ports
Serial COM1 (RS232)
COM2 (RS232); optional
Graphics DVI-I: combined DVI and VGA
USB 4 x USB 2.0 high current
Ethernet 2 x RJ 45 (10/100/1000 Mbps)
PROFIBUS DP 12 Mbps (isolated potential,
compatible to CP 5611), optional
CAN interface Optional
Keyboard, mouse Connected via external USB port
Monitoring and safety functions
Temperature
• When permitted temperature range is exceeded
• Warnings can be analyzed by application program
(local, via LAN)
Watchdog
• Monitoring function for program execution
• Restart can be parameterized in the event of a fault
• Warnings can be analyzed by application program
(local, via LAN)
LED display 4 LEDs for displaying system status
2 of these can be programmed by the user
1
Transient voltage interruption Up to 15 ms buffer time at full load
Buffer memory 2 MB battery-buffered SRAM
1
Software
Operating systems
Available
• Without
• Windows Embedded Standard 2009
• Windows XP Professional MUI SP3 preinstalled
2
Project-specific
• LINUX
• QNX
• VxWorks
• Others on request
• RMOS3 V3.40 (ordered separately)
1
You can find additional information about addressing the LEDs or the SRAM under a
Windows operating system in the section "Output register LED L1/L2". You can find example
programs for addressing the LEDs under Windows XP and under RMOS3 under the FAQ at
the Customer Support site Industry Automation and Drive Technologies - Homepage
(
http://www.siemens.com/automation/service&support).
2
MUI: Multi Language User Interface; 5 languages (English, German, French, Spanish,
Italian)