SIMATIC IPC427C 
Operating Instructions, 04/2009, A5E02414743-01 
91 
Technical specifications 
14
14.1  General specifications 
 
 
General specifications   
Order numbers  see the order documents 
Dimensions    262x142x47 (WxHxD in mm) 
Weight    Approximately 2 kg  
Supply voltage (DC)    24 VDC 
1
 (19.2 to 28.8 V)  
Brief power failure  
according to Namur 
min. 15 ms (at 20.4 V) 
 Max. 10 events per hour; min. 1 s recovery time 
Maximum power consumption  4 A (at 24 V) 
Noise emission  <40dB (A) to DIN 45635-1 
Degree of protection    IP 20 to IEC 60529  
Safety 
Protection class  Protection class I to IEC 61140 
Safety specifications  EN 60950-1; UL 60950; CAN/CSA-C22.2 No. 60950-1; UL 508;  
CAN/CSA-C22.2 No. 142 or CAN/CSA-C22.2 No.14-05 
Electromagnetic compatibility (EMC) 
Emitted interference   EN 61000-6-3 , EN 61000-6-4 , CISPR22:2004 Class B; 
FCC Class A 
Noise immunity:  
Mains borne disturbance variables on supply lines 
+/- 2 kV to IEC 61000-4-4; Burst 
+/-1 kV to IEC 61000-4-5; surge symmetric 
+/- 2 kV to IEC 61000-4-5; Surge asymmetric  
Noise immunity on signal lines  ± -1 kV to IEC 61000-4-4; Burst; Length < 3 m 
± /-2 kV to IEC 61000-4-4; Burst; length > 3 m 
± /-2 kV to IEC 61000-4-5; Surge; length > 30 m  
Immunity to discharges of static electricity  +/-6 kV contact discharge according to IEC 61000-4-2 
-8 kV air discharge according to IEC 61000-4-2  
Immunity to RF interference  10 V/m 80 – 1000 MHz and 1.4 - 2 GHz, 80% AM to  
IEC 61000-4-3 
1 V/m 2 - 2.7 GHz, 80% AM to IEC 61000-4-3 
10 V 10 KHz – 80 MHz, 80% AM to IEC 61000-4-6 
Magnetic field  100 A/m 50/60 Hz according to IEC 61000-4-8  
1
  The generation of the 24 DC V supply voltage by the line-side SV must be made as functional extra-low voltage 
with safe electrical isolation according to  
IEC 60364-4-41 or as SELV in conformity to IEC/UL/EN/DIN-EN 60950-1 and LPS / NEC Class 2.