Replacing hardware
4.3 Procedure for replacing hardware
Compendium Part D - Operation and Maintenance (V9.0)
42 Operating Manual, 02/2018, A5E43228948-AA
Procedure
The exact procedure for a specific component is provided in its accompanying manual. The
table below provides information about the relevant components and associated manuals.
Component
Manual/section
Note
Module of an ET 200SP HA Manual "SIMATIC ET 200SP ET 200SP
HA Distributed I/O System"
1)
, section
"Maintenance"
Interface module of ET 200SP
HA
Manual "SIMATIC ET 200SP HA Inter-
face Module IM 155-6 PN HA
(6DL1155-6AU00-0PM0)"
2)
, section
"Maintenance"
ET 200M interface in a non-
redundant system
Manual "SIMATIC Distributed I/O De-
vice ET 200M"
3)
, section "Maintenance
and service"
You can find possible combinations of bus
module, interface module and configuration
under "New PROFIBUS Interface Modules for
ET 200M, DP/PA Link and Y Link"
4)
.
ET 200M interface in a redun-
dant system
Manual "SIMATIC Distributed I/O De-
vice ET 200M"
3)
, section "Maintenance
and service"
Manual "SIMATIC Fault-tolerant Sys-
tems S7-400H"
5)
, section "Failure and
replacement of components during
operation"
ET 200M module
Manual "SIMATIC Distributed I/O De-
vice ET 200M"
3)
, section "Maintenance
and service"
Please note that the startup time following in-
stallation of the module is longer for fail-safe
modules than for standard ones.
ET 200M redundant module
ET 200M bus module Manual "SIMATIC Distributed I/O De-
vice ET 200M"
3)
, section "Maintenance
and service"
Active bus modules can only be installed on an
IM 1532 if the power supply is interrupted.
You can find possible combinations of bus
module, interface module and configuration
under "New PROFIBUS Interface Modules for
ET 200M, DP/PA Link and Y Link"
4)
.
Connection of DP/PA link and
Y link
Manual "SIMATIC Bus Links DP/PA
Coupler, Active Field Distributors,
DP/PA Link and Y Link"
6)
, section
"Maintenance and service"
You can find possible combinations of bus
module, interface module and configuration
under "New PROFIBUS Interface Modules for
ET 200M, DP/PA Link and Y Link"
4)
.
ET 200iSP interface
Manual "SIMATIC Distributed I/O ET
200iSP"
7)
, section "Replacing the inter-
face module"
Setting and altering the address may require
deletion of the non-volatile parameters on the
interface. This is only possible by shutting off
the power supply. This step may not be possible
in a redundant system.
Set the address of the IM 152 on the module in
advance. This way you can avoid having to shut
down the station. The IM will start up with the
correct address.
ET 200iSP interface in a re-
dundant system