Service and maintenance of SIMATIC PDM
6.6 Replacing/removing field devices
Compendium Part D - Operation and Maintenance (V9.0)
66 Operating Manual, 02/2018, A5E43228948-AA
PA device (PDM V9.1) procedure
In this example, the Siemens SITRANS LR250 level radar revision 2 is replaced with revision
3. The device is configured with the name LR250_Compend in HW Config.
1. Open SIMATIC Manager and select the "Process device plant view" command in the
"View" menu.
SIMATIC PDM opens.
2. Right-click the "LR250_Compend" device and select "Device selection (Reassign)".