Technology functions
3.2 Pulse generators
CPU 1512C-1 PN (6ES7512-1CK01-0AB0)
60 Manual, 12/2017, A5E40898741-AA
Setting and changing the output value (frequency)
You set the frequency with the OUTPUT_VALUE directly with the control program in the
control interface. The value is specified in the real format and the unit is always "Hz". The
possible range depends on the parameter "High-speed output (0.1 A)" as follows:
High-speed pulse output deactivated
Frequency (OUTPUT_VALUE) 0.1 Hz to 10,000 Hz
High-speed pulse output activated
Frequency (OUTPUT_VALUE) 0.1 Hz to 100,000 Hz
Standard output (100 Hz output)
Frequency (OUTPUT_VALUE) 0.1 Hz to 100,000 Hz
The new frequency is applied at the start of the next period. The new frequency has no
impact on the falling edge or the pulse-cycle ratio. However, the application can take up to
10 s depending on the previously set frequency.
Accuracy of the output frequency
The configured output frequency is output with a frequency-dependent accuracy at the digital
output PWM DQA. You can find an overview of the accuracy as a function of the frequency
used in the section Interconnection overview of outputs (Page 111).
Parameters of the frequency output mode
Category
Parameter
Meaning
Value range
Default
Reaction to
CPU STOP
Reaction to CPU
STOP
The parameter "Output substitute
value" generates a substitute
value upon CPU STOP, which you
can define with the parameter
"Substitute value for pulse output
(DQA)".
Output substitute value
Output substi-
tute value
The parameter "Continue opera-
tion" still generates the frequency
output signal upon CPU STOP,
which was generated before the
CPU STOP.
Continue operation
Substitute value
for pulse output
(DQA)
If you have set the option "Output
substitute value" for "Reaction to
CPU STOP", the parameter "Sub-
stitute value for pulse output
(DQA)" defines the substitute
value to be used for the pulse
output of the channel.
If you have set the option "Contin-
ue operation" for "Reaction to CPU
STOP", the parameter "Substitute
value for pulse output (DQA)"
cannot be selected.
0
(use substitute value 0)
0
1
(use substitute value 1)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Simatic S7-1500 CPU 1512C-1 PN and is the answer not in the manual?

Siemens Simatic S7-1500 CPU 1512C-1 PN Specifications

General IconGeneral
Integrated InterfacesPROFINET
Data Memory1 MB
Number of Signal Boards1
Firmware VersionV2.8
Rated Value (DC)24 V
Number of PROFINET Ports2
Number of PROFINET Ports with Switch2
Integrated Web ServerYes
Number of Digital Inputs16
Number of Digital Outputs16
Number of Analog Outputs2
Number of High-speed Counters6
Program Memory300 KB
Number of Signal Modules32
Engineering withSTEP 7 Professional V13
Interface TypeEthernet
Data StorageYes
Operating Temperature0 to 60 °C
Dimensions147 mm x 129 mm