Commissioning
3.3 Preparing the connection to the SINAMICS
Connection of the SINAMICS S120 to the Technology CPU
Product Information, 09/2011, A5E00480378-04
25
Technology CPU: Configuring PROFIBUS DP (DRIVE)
1. After selecting the Technology CPU, the "Properties - PROFIBUS interface DP(DRIVE)
(R0/S3.1)" dialog box will be displayed. Click the "New" button to create a new
PROFIBUS network there.
2. In the "Network settings" tab of the "PROFIBUS Properties" dialog, set the following
properties:
Highest PROFIBUS address: 2
The setting of the highest PROFIBUS address should correspond to the highest
address of an active PROFIBUS node. This setting reduces the PROFIBUS time to
search for a new active PROFIBUS node.
Transmission rate: 12 Mbps
This transmission rate permits the largest possible data throughput on the PROFIBUS.
Pay attention, however, to the maximum transmission rate of the CP in the
programming device. If the value is set too large, access to the CPU will no
longer be possible.
Profile: "User-defined"
The "user-defined" setting is required, when a message frame extension with
BICO wiring is required in addition to the standard message frames.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)