Technical specications X27 (RS 422/485) interface
The following table contains the technical specications of the X27 (RS 422/ 485) interface of
the CP 440-RS 422/485.
Table 10-1 Technical specications of the X27 (RS 422/485) interface
Technical specications
Interface RS 422 or RS 485, 15-pin sub D female
RS 422 signals
RS 485 signals
TXD (A), RXD (A), TXD (B), RXD (B), GND
R/T (A), R/T (B), GND
all isolated against the S7-internal power supply (backplane bus) and the
external 24 V DC supply
Max. distance 1200 m
Max. baud rate 115200 bps
Technical specications of the 3964(R) procedure
The following table contains the technical specications of the 3964(R) procedure.
Table 10-2 Technical specications of the 3964(R) procedure
3964(R) procedure with default values
Max. message frame
length
400 bytes (see chapter "Overview of the Function Blocks (Page 73)")
Parameter can be assigned parameters:
• With/without block check character
• Priority: low/high
• Transmission rate: 300, 600, 1200, 2400, 4800, 9600, 19200, 38400,
57600, 76800, 115200 bps
• Character frame: 9, 10, 11 or 12 bits
• Initial state of receive line: none, R(A)5V/R(B)0V, R(A)0V/R(B)5V
• Number of buered message frames: 1 to 10, use entire buer
3964(R) procedure, can be assigned parameters
Technical specications
10.1 Technical Specications of the CP 440
Point-to-point connection CP 440 Installation and Parameter Assignment