832-6063.0 * INSTALLATION SIMOSEC * REVISION 02 65
Installation
15 Switchgear extension
If required, installed switchgear can be extended with additional panels, or the existing
panel configuration can be modified. After disconnecting and grounding the electric
circuits, and after discharging any stored-energy in operating mechanisms, additional
panels can be installed and connected. The procedure to be followed for switchgear
extension is the same as for first installation
16 Placing SIMOSEC switchgear into service
16.1 Safety instructions
The correct and safe operation of this switchgear is conditional on:
• Proper transportation
• Correct storage
• Correct assembly and installation
• Careful operation in accordance with established procedures which comply with appli-
cable codes and regulations
• Use of proper Personal Protective Equipment (PPE) (see NFPA 70E)
16.2 Instructing the operating personnel
Ö The operating personnel should have these instructions available.
Ö Instruct operating personnel in theory and practice of switchgear operation.
Ö Ensure that the operating personnel are familiar with all operational details when
placing equipment into service.
16.3 Checking the assembly work and the accessories
Accessories supplied with the equipment:
• Operating instructions
• Operating levers for three-position switch
• Double-bit keys (if necessary)
• Circuit diagrams
• Voltage detector or voltage detection system
Ö Ensure that the above listed accessories are easily accessible.
Ö Ensure that the assembly work has been performed correctly (see sections 12 - 14).
Ö Ensure that all covers have been installed and enclosure hardware torqued to the
correct values.
Ö Ensure that all electrical connections have been torqued to the correct values.