Motor data identification Select the method which the inverter uses to measure the data of the
connected motor:
OFF: No motor data identification
STIL ROT: Measure the motor data at standstill and with the motor rotating.
The inverter switches off the motor after the motor data identification has been completed.
STILL: Recommended setting: Measure the motor data at standstill.
The inverter switches off the motor after the motor data identification has been completed.
Select this setting if the motor cannot freely rotate, e.g. for a mechanically limited traversing
range.
ROT: Measure the motor data while the motor is rotating.
The inverter switches off the motor after the motor data identification has been completed.
ST RT OP: setting same as STIL ROT.
The motor accelerates to the currently set setpoint after the motor data identification.
STILL OP: setting same as STILL.
The motor accelerates to the currently set setpoint after the motor data identification.
Complete quick commissioning as follows:
1. Switchover the display using an arrow key: nO → YES
2. Press the OK key.
You have completed quick commissioning.
5.4.4 Dynamic Drive Control
Select the motor standard:
KW 50HZ: IEC
HP 60HZ: NEMA
KW 60HZ: IEC 60 Hz
Set the inverter supply voltage.
Select the motor type. If a 5-digit motor code is stamped on the motor rating plate, select the
corresponding motor type with motor code.
Motors without motor code stamped on the rating plate:
INDUCT: Third-party induction motor
1L… IND: 1LE1, 1LG6, 1LA7, 1LA9 induction motors
Motors with motor code stamped on the rating plate:
1LE1 IND 100: 1LE1 . 9
1PC1 IND: 1PC1
1PH8 IND: Induction motor
Depending on the inverter, the motor list in BOP-2 can deviate from the list shown above.
3
027,'
),1,6+
3
(8586$
3
,1992/7
3
0277<3(
Commissioning
5.4 Quick commissioning using the BOP-2 operator panel
SINAMICS G120C converter
126 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF