10.10.3 Output reactor
Preconditions for using reactors:
● Maximum permissible output frequency of the inverter: 150 Hz
● Inverter pulse frequency: 4 kHz
The assignment of a suitable output reactor to the inverter is provided in the following Chapter:
Optional components (Page 36)
Dimensions and mounting dimensions:
Mounting base components (Page 47)
Mounting the output reactor (Page 59)
Table 10-19 Technical data of the output reactor
Article no. 6SE6400-3TC00-4AD2 6SL3202-0AE16-1CA0 6SL3202-0AE18-8CA0
Inductance 2.5 mH 2.5 mH 1.3 mH
Power loss at 50/60 Hz 25 W 90 W 80 W
Degree of protection IP20 IP20 IP20
Weight 0.8 kg 3.4 kg 3.9 kg
Table 10-20 Technical data of the output reactors
Article no. 6SL3202-0AE21-8CA0 6SL3202-0AE23-8CA0 6SE6400-3TC07-5ED0
Inductance 0.54 mH 0.26 mH 0.3 mH
Power loss 80 W 110 W 277 W
Degree of protection IP20 IP20 IP20
Weight 10.1 kg 11.2 kg 26.7 kg
Table 10-21 Technical data of the output reactors
Article no. 6SE6400‑3TC14‑5FD0 6SL3000‑2BE32‑1AA0 6SL3000‑2BE32‑6AA0
Inductance 0.2 mH --- ---
Power loss 469 W 486 W 500 W
Degree of protection IP20 IP00 IP00
Weight 55.9 kg 60 kg 66 kg
Technical data
10.10 Accessories
SINAMICS G120C converter
424 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF