10.10.5 dU/dt filter plus Voltage Peak Limiter
The du/dt filter plus Voltage Peak Limiter limits the rate of voltage rise at the inverter output to
values < 500 V/µs - and the voltage peaks at the rated line voltages to values < 1000 V:
The assignment of the "du/dt filter plus Voltage Peak Limiter" to the inverter is provided in the
following Chapter:
Optional components (Page 36)
Dimensions and mounting dimensions:
Mount dU/dt filter plus Voltage Peak Limiter (Page 62)
Table 10-23 Technical data "dU/dt filter plus Voltage Peak Limiter"
Article no. 6SL3000-2DE32-6AA0
Power loss 730 W
Degree of protection IP00
Weight 72 kg
Technical data
10.10 Accessories
SINAMICS G120C converter
426 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF