EasyManua.ls Logo

Siemens SINAMICS G120C USS/MB - Drive Control Via Ethernet;Ip

Siemens SINAMICS G120C USS/MB
470 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.8 Drive control via Ethernet/IP
EtherNet/IP is an Ethernet-based fieldbus. EtherNet/IP is used to transfer cyclic process data
as well as acyclic parameter data.
Settings for Ethernet/IP
Parameter Explanation
p2030 = 10 Fieldbus interface protocol selection: Ethernet/IP
p8920 PN Name of Station
p8921 PN IP address (Factory setting: 0)
p8922 PN default gateway (factory setting: 0)
p8923 PN Subnet Mask (Factory setting: 0)
p8924 PN DHCP mode (Factory set‐
ting: 0)
0: DHCP off
2: DHCP on, identification based on MAC address
3: DHCP on, identification based on Name of Station
p8925 PN interface configuration
(Factory setting: 0)
0: No function
1: Reserved
2: Save the configuration and activate
3: Delete configuration
p8980 Ethernet/IP profile (Factory setting: 0)
A change only becomes effective after the inverter power
supply has been switched off and switched on again.
0: SINAMICS
1: ODVA AC/DC
p8982 Ethernet/IP ODVA speed scaling (Factory setting: 128)
A change only becomes effective after the inverter power supply has been switched off
and switched on again.
123: 32
124: 16
125: 8
126: 4
127: 2
128: 1
129: 0.5
130: 0.25
131: 0.125
132: 0.0625
133: 0.03125
Further information
Further information about USS is provided in the "Fieldbus" function manual.
Overview of the manuals (Page 459)
Advanced commissioning
6.8 Drive control via Ethernet/IP
SINAMICS G120C converter
200 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF

Table of Contents

Related product manuals