6.16.5 Fixed speed setpoint as setpoint source
In many applications after switching on the motor, all that is needed is to run the motor at a
constant speed or to switch between different speeds.
Example: After it has been switched on, a conveyor belt only runs with two different velocities.
Interconnecting a fixed speed setpoint with the main setpoint
)L[HGVSHHGVHWSRLQW
6HOHFW
)L[HGVSHHGVHWSRLQW
)L[HGVSHHGVHWSRLQW
)L[HGVSHHGVHWSRLQW
)L[HGVSHHG
VHWSRLQWHIIHFWLYH
0DLQVHWSRLQW
$GGLWLRQDOVHWSRLQW
U
S
S
Figure 6-36 Fixed speed setpoint as setpoint source
Table 6-37 Setting the fixed speed setpoint as setpoint source
Parameter Remark
p1070 = 1024 Main setpoint
Interconnect main setpoint with fixed speed setpoint.
Selecting the fixed speed setpoint, either direct or binary
The inverter makes a distinction between two methods when selecting the fixed speed
setpoints:
Directly selecting a fixed speed setpoint
You set 4 different fixed speed setpoints. Up to 16 different setpoints are obtained by adding
one or several of the four fixed speed setpoints.
)L[HGVHWSRLQWVHOHFWLRQELW
)L[HGVHWSRLQWVHOHFWLRQELW
)L[HGVHWSRLQWVHOHFWLRQELW
)L[HGVHWSRLQWVHOHFWLRQELW
)L[HGVHWSRLQW
)L[HGVHWSRLQW
)L[HGVHWSRLQW
)L[HGVSHHGVHWSRLQW
HIIHFWLYH
)L[HGVHWSRLQW
U




S
S
S
S
S
S
S
S
Figure 6-37 Simplified function diagram when directly selecting the fixed speed setpoints
Additional information about direct selection can be found in function diagram 3011 in the List
Manual.
Advanced commissioning
6.16 Setpoints
SINAMICS G120C converter
240 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF