6.16.2 Analog input as setpoint source
Interconnecting an analog input
If you have selected a pre-assignment without a function of the analog input, then you must
interconnect the parameter of the main setpoint with an analog input.
$QDORJLQSXW
DFWXDOYDOXH
0DLQVHWSRLQW
6XSSOHPHQWDU\VHWSRLQW
S
S
$,
$,
U>@
Figure 6-32 Example: Analog input 0 as setpoint source
Table 6-33 Setting with analog input 0 as setpoint source
Parameter Remark
p1070 = 755[0] Main setpoint
Interconnect the main setpoint with analog input 0
p1075 = 755[0] Additional setpoint
Interconnect the additional setpoint with analog input 0
Advanced commissioning
6.16 Setpoints
SINAMICS G120C converter
236 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF