7.1.3 Transferring the setting from the memory card
Automatically transferring
Precondition
The inverter power supply has been switched off.
Procedure
Proceed as follows to automatically transfer your settings:
1. Insert the memory card into the inverter.
2. Then switch on the inverter power supply.
If there is valid parameter data on the memory card, then the inverter accepts the data from
the memory card.
Manually transferring
Requirements
The inverter power supply has been switched on.
No memory card is inserted in the inverter.
Procedure with STARTER
Proceed as follows to transfer settings from a memory card to the inverter:
1. Go online and in your drive, select the "Drive Navigator".
2. Select the "Commissioning" button.
3. Select the button to transfer the data from the memory card to the inverter.


Saving settings and series commissioning
7.1 Saving settings on a memory card
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF 327