EasyManua.ls Logo

Siemens SINAMICS G120C USS/MB - Correcting an Unsuccessful Firmware Upgrade or Downgrade

Siemens SINAMICS G120C USS/MB
470 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9.3.3 Correcting an unsuccessful firmware upgrade or downgrade
How does the inverter signal an unsuccessful upgrade or downgrade?
5'<
%)
The inverter signals an unsuccessful firmware upgrade or downgrade
by a quickly flashing LED RDY and the lit LED BF.
Correcting an unsuccessful upgrade or downgrade
You can check the following to correct an unsuccessful firmware upgrade or downgrade:
Does the firmware version of your inverter fulfill the preconditions?
For an upgrade, as a minimum V4.5.
For a downgrade, as a minimum V4.6.
Have you correctly inserted the card?
Does the card contain the correct firmware?
Repeat the appropriate procedure.
Corrective maintenance
9.3 Firmware upgrade and downgrade
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF 397

Table of Contents