EasyManua.ls Logo

Siemens SINAMICS G120C USS/MB - Advanced Settings

Siemens SINAMICS G120C USS/MB
470 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.19.3.3 Advanced settings
Special settings for a pulling load
For a pulling load, e.g. a hoisting gear, a permanent force is exerted on the motor, even when
the motor is stationary.
For a pulling load, we recommend that you use vector control with an encoder.
If you use encoderless vector control with a pulling load, then the following settings are required:
Set the following parameters:
Par. Explanation
p1750 Motor model configuration
Bit 07 = 1 Use speed switchover limits that are less sensitive to external effects
p1610 Static torque setpoint (encoderless) (Factory setting: 50 %)
Set a value which is higher than the maximum load torque that occurs.
When opening the motor holding brake, enter a speed setpoint > 0.
For speed setpoint = 0, and with the motor holding brake open, the load drops because the
induction motor rotates with the slip frequency as a result of the pulling load.
Set the ramp-up and ramp-down times ≤ 10 s in the ramp-function generator.
If, in quick commissioning, you have selected application class Dynamic Drive Control then
set p0502 = 1 (technological application: dynamic starting or reversing).
Advanced commissioning
6.19 Motor control
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF 273

Table of Contents

Related product manuals