6.16.3 Specifying the setpoint via the fieldbus
Interconnecting the fieldbus with the main setpoint
5HFHLYHGGDWD
0DLQVHWSRLQW
$GGLWLRQDOVHWSRLQW
U>@
3='
3='
S
S
Figure 6-33 Fieldbus as setpoint source
Most standard telegrams receive the speed setpoint as a second process data PZD2.
Table 6-34 Setting the fieldbus as setpoint source
Parameter Remark
p1070 = 2050[1] Main setpoint
Interconnect the main setpoint with process data PZD2 from the fieldbus.
p1075 = 2050[1] Additional setpoint
Interconnect the additional setpoint with process data PZD2 from the fieldbus.
Advanced commissioning
6.16 Setpoints
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF 237